Pressure Reducing Valve YAWM-1
Applicable fluid: Fresh water, Industrial water, Agricultural water
Primary applied pressure:
-Nominal diameter 200 to 250 : 0.05 to 0.69 MPa
-Nominal diameter 300 to 400 : 0.05 to 0.34 MPa , 0.29 to 0.69 MPa
Applicable fluid temperature: 80℃ or less
Connection : KS 10K RF FLANGE /JIS 10K RF
Body: GC200
Disc, Seat : NBR, CAC406
Diaphragm: NBR
Body pressure test: Water pressure 1.5MPa (option:Body: GC200)
Disc, Seat : NBR, CAC406
YAWM-1 Type Primary Pressure Regulating Valve
The type YAWM-1 primary pressure regulating valve combines a main valve and an auxiliary valve. The main valve is operated by setting the pressure of the auxiliary valve.
As a bypass valve for large capacity pumps, it discharges the increased amount of pressure resulting from load fluctuations and ensures that the discharge pressure of a pump remains constant.