General Features
Codes And Standars
Pilot operated pressure relief valve able to operate at considerably higher set pressure than with spring loaded safety relief valves, the valve operation and lift are unaffected by back-pressure
European Directive: | 2017 / 68 / UE |
European Directive: | 2014/34/UE (ATEX). |
Design: | EN ISO-4126-1 & ASME VIII Div. 1 |
Certifications: | PED Modul B+D / ASME “UV” & “NB” |
Pressure & Temperature Limits: | API 526 & ASME B16.34 |
Tests: | API 527 & ASME B16.34 |
Quality system | EN ISO -9001-2015 |
Materials: | ASTM / ASME & EN |
Sizes And Ratings
Standard |
ASME |
EN
- ISO |
Sizes: |
1” x 2” up to 8” x 10” |
DN-25 x DN-50 up to DN-200 x DN-250 |
Rating: |
150# up to 2500# |
PN-10 up to PN-420 |
Performance
Pilot P01S | P01M |
Action Snap / Pop | Modulating |
Type Non flowing | Non flowing |
Min ÷ Max set pressure [ barg ] 3.5 ÷ 155 | 1 ÷ 155 |
Full lift overpressure 2% of Pset | 0.1 bar or 5% whichever is the greater |
Backpressure | |
Maximum pressure at pilot outlet 65% of Pset | 65% of Pset |
Min ÷ Max relieving temperature [ °C (°F) ] -40 (-40) ÷ 200 (392) | -40 (-40) ÷ 200 (392) |
Media Gas ÷ Steam ÷ Liquid | Gas ÷ Steam ÷ Liquid |
Back-Flow Preventer | 01P Available Built -in Standard | 01MP Available Built -in Standard | |
Field Test Arrangement | | | |
Lifting Lever | | Over 60°C (140°F) |
(140°F) |
Manual Blowdown Valve | | For steam service |
service |
Internal Pressure Pick-up | | | |
Remote Sensing | | | |
Device for remote warning of valve opening | | |
Post a Comment
Your comment will be reviewed before publication